Friday, August 27, 2010
The water main installation is complete, filling and pressure testing has been done and the new main is being chlorinated and tested. Test results should be in Tuesday and then the contractor will begin water service installations to each home. On the day the contractor works on your service they will knock on the door to notify residents of the water shutoff. At the same time, the contractor is doing sewer repairs across the roads which necessitate road closures at that location.
Friday, August 20, 2010
Water main installation is nearing completion. Once everything is installed, the contractor will perform a pressure test. For the test, the main is filled with water and pressurized to 150 pounds per square inch (psi). To pass the pressure test, pressure must be held at 150 psi for 2 hours. Once the pressure test passes, the water main gets chlorinated. Once the chlorination tests pass, the contractor can begin on water services. Contractor is going to start on storm sewers while waiting for the water main testing.